42
5.3 non-combustible facing material for CB36 / CX36-1
WARNING: Non-combustible facing material must not project more than 4” (101.6mm) from the face of
EN the door (all three sides). If greater projections are desired, increase the clearance to the sides and
top by 2” (50.8mm) for every additional 1” (25mm) of projection. If using an optional surround, the
same rule applies, starting from the top of the surround. Ensure clearances are maintained for
surround removal, as it must lift off the appliance for maintenance.
4" (10.2cm)
TOP OF
APPLIANCE
GLASS
DOOR
5.4 alcove clearances
RECESS OR
ALCOVE
AREA
ENCLOSURE
AREA
APPLIANCE
NOTE: Recesses or alcoves above the appliance can be made as deep as desired provided the
minimum clearances to combustibles are maintained.
Non-combustible material can be used, provided the minimum clearances to combustible materials are applied
The minimum enclosure volume must be increased by no less than the volume of the recess. This
adjustment can be made by increasing any or all of the height, width and depth of the enclosure.
W415-1679 / D / 03.09.18