Under fault conditions or even if the Panel is powered down, this output will be switch to O volts.
Ensure the polarity of the connections is observed at all times and end of line resistors ( 6K8 5% )
are fitted for correct operation.
Delays to outputs (Option 7.11 of EN54pt 2)
The Panel has the option to delay the operation of panel sounders, the fire routing equipment
output and the fire protecting Equipment. This delay is selectable using the site installer download
software .The delay is configurable in increments of 1 minute up to a maximum of 10 minutes.
This delay can be enabled and disabled at access level 2.
The Panel has the facility for a specific call point to override this delay by programming this call
point via an input interface to provide an evacuate signal using site Installer.
Coincidence Detection (Option 7.12 of EN54 pt 2)
The Panel has the facility to inhibit the operation of the output sounders, Output to Fire routing
equipment and the output of the fire protecting equipment until one more confirmatory signals are
received from different zones. This feature is programmable using Site Installer Software.
Alarm Counter (Option 7.13 of EN54 pt2)
The Panel has provision to record the number of instances that the CIE enters the fire alarm
condition.
The information is available at access level 2.
TEST (Option 16 of EN54)
The Panels equipped with the test option and can be implemented by either Zone or Address.
Alarm Verification
The Panel has the facility for global alarm verification where the detector alarm decision is
integrated over 30 seconds.
Optional Functions as per EN54 P2&4Optional Functions as per EN54 P2&4