4.1: General Wiring Instructions
4.1.1: Electrical Codes and Warnings
Be sure that all wiring complies with the National Electrical Code (NEC) or its national equivalent,
and all prevailing local codes.
DANGER: Hazardous voltages.
Exercise caution when installing and adjusting.
Failure to heed this warning can cause equipment damage, injury, or death.
High-voltage circuits connected to mains power.
XE2/XP2/XM2/800-1818/800-1819/800-1887
Failure to heed this warning can cause equipment damage, injury, or death.
Refer to the Xenus Plus Dual-Axis STO User Manual
The information provided in the Xenus Plus Dual-Axis STO User Manual must be considered
for any application using the XE2/XP2/XM2/800-1818/800-1819/800-1887 drive STO feature.
Failure to heed this warning can cause equipment damage, injury, or death.
Do not plug or unplug connectors with power applied.
The connecting or disconnecting of cables while the drive has 24Vdc and/or mains power
applied is not recommended.
Failure to heed this warning may cause equipment damage.
Do not ground mains-connected circuits.
Do not ground Mains connected circuits: J1, J2, J3 and J4 for XE2/XP2/XM2/800-1818/800-
1819/800-1887; J1, J2 and J3 for XEL/XPL/XML.
Failure to heed this warning can cause equipment damage.
Risk of Radio Frequency Interference
The Xenus Plus Dual Axis drives are not intended for use on a low-voltage public network
which supplies domestic premises.
Radio frequency interference should be expected if used on such a network
EMI Line Filter is necessary to meet EMC requirements
Use if an EMI Line Filter with Xenus Plus Dual Axis drives is mandatory for meeting EMC
requirements
A surge protection device (SPD) or isolation transformer is required to establish an
over-voltage category II environment
The AC mains supplying the XE2/XP2/XM2/800-1818/800-1819/800-1887 drives must be
limited to over-voltages of Category II. The relevant standards assume AC mains with over-
voltages per OVC III. An SPD or an isolation transformer is required to limit over-voltages to
OVC II levels. The surge protection requirement is limited to models certified to IEC 61800-5-
1 and UL 61800-5-1. The XEL/XPL/XML models are certified to IEC 61010-1 and UL 61010-1
and do not require surge protection.