Xenus Plus User Guide 16-01344 Rev 06
Copley Controls 89
AC Mains Wiring Diagram (Three-Phase) XEL/XPL/XML
4.2.2: XE2/XP2/XM2/800-1818/800-1819/800-1887
Mating Connector
Euro-style 5.08 mm pluggable female terminal block.
12 AWG, 600 V
Shielded cable required for CE compliance
Wire Insertion/Extraction Tool
Connector and tool are included in Connector Kits XE2-CK, XP2-CK and XM2-CK.
AC power input (hot or L1)
AC power input (neutral or L2)
AC Mains Fuse Recommendation (All Xenus Plus models)
Recommended fuse type: Class CC, 600 Vac rated, Ferraz-Shawmut ATDR, Littelfuse CCMR,
Bussman LP-CC, or equivalent.
EMI Line Filter is necessary to meet EMC requirements
Use of an EMI Line Filter with Xenus Plus Dual Axis drives is mandatory for meeting
EMC requirements
A surge protection device (SPD) or an isolation transformer is required to
establish an over-voltage category II environment
The AC mains supplying the drive must be limited to over-voltages of Category II. The
relevant standards assume AC mains with over-voltages per OVC III. An SPD or an
isolation transformer is required to limit over-voltages to OVC II levels.