Xenus Plus User Guide 16-01344 Rev 06
Copley Controls 94
4.4.2: (J2) XE2/XP2/XM2/800-1819
With the exception of model 800-1818, 800-1887 and “-N” models, the Xenus Plus Dual Axis models are
provided with an integrated regen resistor that is pre-wired and connected to J2. If a given application
requires a higher capacity regen resistor, then the user may disconnect the integrated resistor from J2 and
connect an external resistor instead. An external regen resistor may be used with model 800-1818.
Connection details for both the integrated and external regen resistors are provided as follows.
Mating Connector
Description
Euro-style, 3 position, 5.08 mm pluggable female terminal block.
Manufacturer PN
Wago: 231-303/107-000
Wire Size
22 - 12 AWG
Recommended Wire
12 AWG, 600 V
Shielded cable required for CE compliance
Wire Insertion/Extraction Tool
Wago: 231-131 or 231-291
Standard connector and tool are included in Connector Kits XE2-CL, XP2-CK and XM2-CK.
Pin Description
Pin
Signal
Function
1
Regen +
+ DC Bus to one side of regen resistor
2
Regen -
Collector of regen transistor to one side of regen resistor
3
Frame ground
Enclosure ground and cable shield
WARNING
The mating connector must be installed at location J2 regardless of whether a
regen resistor is connected
A mating connector must be installed at location J2 whenever AC mains power is
applied and within the capacitor discharge time. Otherwise the terminals of J2 are
exposed and present a shock hazard under these conditions.
Wiring Diagram Integrated Regen Resistor
!