Xenus Plus User Guide 16-01344 Rev 06
Copley Controls 94
4.4.2: (J2) XE2/XP2/XM2/800-1819
With the exception of model 800-1818, 800-1887 and “-N” models, the Xenus Plus Dual Axis models are
provided with an integrated regen resistor that is pre-wired and connected to J2. If a given application
requires a higher capacity regen resistor, then the user may disconnect the integrated resistor from J2 and
connect an external resistor instead. An external regen resistor may be used with model 800-1818.
Connection details for both the integrated and external regen resistors are provided as follows.
Mating Connector
Euro-style, 3 position, 5.08 mm pluggable female terminal block.
12 AWG, 600 V
Shielded cable required for CE compliance
Wire Insertion/Extraction Tool
Standard connector and tool are included in Connector Kits XE2-CL, XP2-CK and XM2-CK.
+ DC Bus to one side of regen resistor
Collector of regen transistor to one side of regen resistor
Enclosure ground and cable shield
The mating connector must be installed at location J2 regardless of whether a
regen resistor is connected
A mating connector must be installed at location J2 whenever AC mains power is
applied and within the capacitor discharge time. Otherwise the terminals of J2 are
exposed and present a shock hazard under these conditions.
Wiring Diagram – Integrated Regen Resistor