EasyManua.ls Logo

CPS SCA Series - Page 116

Default Icon
164 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
108
Table 6-17 Reactive Power Control (IEEE-1547 / Rule21 and ISO-NE)
Only for CPS SCA50/60KTL-DO/US-480
Grid Reactive Power
Derating
Setting Range
Parameter
name
Description
IEEE1547
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min
Default
Max
QuCurveU1
(V)
Voltage of Q(U) Curve point
1
100
107.9
110
100
103.3
110
100
107.99
110
QuCurveQ1
(%)
Reactive power of Q(U)
Curve point 1
-66
0
66
-66
0
66
-66
0
66
QuCurveU2
(V)
Voltage of Q(U) Curve point
2
100
110
110
100
107
110
100
110
110
QuCurveQ2
(%)
Reactive power of Q(U)
Curve point 2
-66
-50
55
-66
-30
66
-66
-50
66
QuCurveU1i
(V)
Voltage of Q(U) Curve point
1i
90
92.01
100
90
96.7
100
90
92.01
100
QuCurveQ1i
(%)
Reactive power of Q(U)
Curve point 1i
-66
0
66
-66
0
66
-66
0
66
QuCurveU2i
(V)
Voltage of Q(U)Curve point
2i
80
90
92
80
92
92
80
90
92
QuCurveQ2i
(%)
Reactive power of
Q(U)Curve point 2i
-66
50
66
-66
30
66
-66
50
66
QuCurveTriP
ower (V)
The trigger of Q(U)Curve
5
20
100
5
20
100
5
20
100
QuCurveUnd
oPower (V)
The end of Q(U)Curve
5
5
100
5
5
100
5
5
100
CtrMode
The control mode of reactive
power
0: Disable dispatch mode.
1: Remote dispatch mode.
2: Local control, by Q
3: Local control, by PF
4: PF(P) curve
5: Q(U) curve
0
0
5
0
5
5
0
0
5
Percentage
Local Power Factor Setting
-66
0
66
-66
0
66
-66
0
66

Table of Contents