150
10.2 Measurement Tolerances
The data supplied by the inverter may differ from measurements taken by
certified measuring instruments (e.g. output meters, multimeters and grid
analysers). The inverter is not a measuring instrument and has wider
tolerances for the measurements it makes.
The inverter tolerances are generally:
±5% for real-time measurements with output power below 20% nominal
power
±3% for real-time measurements with output power above 20% nominal
power
±4% for all statistical data
CPS inverter tolerances are specified below:
Voltage tolerances: ±1%
Current tolerances: ±2%
Frequency tolerances: ±0.5%
Power tolerances: ±3%
Time tolerances: ±1%
Temperature tolerances: ±2degC