EasyManua.ls Logo

CPS SCA Series - Page 124

Default Icon
164 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
116
Other Parameters
Setting Range
Parameter
Name
Description
IEEE1547
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min
Defaul
t
Max
GFCIStaticT (s)
The static
threshold time of
Leakage current
0
0.20
655
0
0.20
655
0
0.20
655
GFCIDynProFa
ctor
The dynamic
trigger coefficient
of Leakage current
0
100
200
0
100
200
0
100
200
DCIProtection1
Maximum DCI
value1
0.01
2.50
5
0.01
2.50
5
0.01
0.50
5
DCIProtectio
nT1 (s)
Trip time 1 of
DCI
0
10
120
0
10
120
0
60
120
DCIProtectio
n2 (mA)
Maximum DCI
value2
5
950
5000
5
950
5000
5
950
5000
DCIProtection
T2 (s)
Trip time 2 of
DCI
0
1
120
0
1
120
0
1
120
PVStartVolt(
V)
PV start-up
voltage
300
330
400
300
330
400
300
330
400
MPPTScan
Period (s)
MPPT Scan
Cycle
300
3600
5400
300
3699
5400
300
3600
5400
ISOProtectio
n (Ω)
Minimum
insulation
resistance
1k
100k
2000k
1k
100k
2000k
1k
100K
2000k
StarUPMinT
emp (C)
The minimum
startup
temperature
-35
-30
-20
-35
-30
-20
-35
-30
-20
Duplication
Group
Parameter of
repetitive
control
0
30
100
0
30
100
0
0
100
CtrParaGrou
p
The enabled
control
parameters
group.
0
4
4
0
4
4
0
4
4
Island
Protect
Island
enable/disabl
0
1
1
0
1
1
0
1
1

Table of Contents

Related product manuals