Table 7-3 LCD Troubleshooting ALARM
Fault Description / Instruction
Definition: Prompt detection of abnormal temperature
Possible causes:
1. Temperature Sensor socket connecter has poor
contact
2. Temperature Sensor is damaged
Recommended solutions:
1. Observe temperature display
2. Switch off exernal AC disconnect, then back on to
reboot the system;
3. Contact post-sales service if not corrected
Definition: Communication inside inverter fails
Possible causes:
Terminal block connecters of internal communication wires
have poor contact
Recommended solutions:
1. Observe for 5 minutes to see whether the alarm will be
eliminated automatically
2. Switch off exernal AC disconnect, then back on to
reboot the system
3. Contact post-sales service if not corrected
Definition: Cooling fan failure
Possible causes:
1. Fan is blocked
2. Fan service life has expired
3. Fan socket connecter has poor contact
Recommended solutions:
1. Observe for 5 minutes to see whether the alarm will be
eliminated automatically
2. Check for foreign objects on fan blades;
3. Switch off exernal AC disconnect, then back on to
reboot the system
4. Contact post-sales service if not corrected
Definition: Internal alarm
Possible causes:
Internal memory has a problem
Recommended solutions:
1. Observe for 5 minutes to see whether the alarm will be
eliminated automatically
2. Contact post-sales service if not corrected