9
Grid Adaptability: IEEE 1547 Interconnect Standard and CPUC Rule
21 applicable; Reactive Power; >0.99 PF (±0.8 adjustable), Selectable
Apparent Power rating enables Full Active Power rating to +/-0.91 PF,
and optional local or remote Active Power Curtailment.
Flexible Communication: Supports standard CPS Modbus RS485,
SunSpec Modbus, and HTTPS/XML communications via Flex Gateway
to ensure compatibility with 3rd party monitoring and control systems.
The Flex Gateway card enables further command/control as well as
remote firmware upgrades. (Flex Gateway card is optional accessory.
Refer to Flex Gateway manual for further detailed information.)
Wide DC input voltage range: Operating DC Input Voltage Range:
200-950VDC; Max DC input voltage: 1000VDC.
Long Service Life: Designed with thin-film capacitors to extend
inverter's service life.
3 MPPTs: Multi-channel MPPT (Maximum Power Point Tracker) enables
maximum design flexibility and energy harvest optimization over the life
of the system.
Separable Wirebox: The wirebox enables fused input of either discrete
wiring using the Standard wirebox, SCA50/60KTL-DO/US-480 optional
rapid shutdown wirebox with integrated Sunspec PLC transmitter for use
with APS、TS4-F integrated smart modules and APS、Tigo TS4-A-F
products, SCA25KTL-DO/US-208 have rapid shutdown wirebox with
integrated Sunspec PLC transmitter for use with APS smart modules
and APS products.
High Protection Degree: Powder coated aluminum NEMA 4X
enclosure meets the demanding needs of both indoor and outdoor use.
Intelligent Integration: Integrated DC/AC disconnect switches, and up
to 15 fused string inputs eliminate the need for external DC combiner