86
Table 6-2 Protection Parameters (IEEE1547 and Rule21)
Only for CPS SCA25KTL-DO-US-208
Grid Voltage Protection
Setting Range
Parameter name
Description
(Threshold Value of)
IEEE1547
Rule21
Min
Default
Max
Min
Default
Max
GridVoltMax1(%)
Level 1 Max. grid
voltage
100.00
110.00
135.00
100.00
110.00
135.00
VoltMaxTripTime1(S)
Level 1 Max. grid trip
voltage
0.00
1.00
655.00
0.00
1.00
655.00
GridVoltMax2(%)
Level 2 Max. grid
voltage
100.00
120.00
135.00
100.00
120.00
135.00
VoltMaxTripTime2(S)
Level 2 Max. grid trip
voltage
0.00
0.16
655.00
0.00
0.16
655.00
GridVoltMax3(%)
Level 3 Max. grid
voltage
100.00
120.00
135.00
100.00
120.00
135.00
VoltMaxTripTime3(S)
Level 3 Max. grid trip
voltage
0.00
0.16
655.00
0.00
0.16
655.00
GridVoltMin1
(%)
Level 1 Min. grid voltage
30.00
88.00
100.00
30.00
88.00
100.00
VoltMinTripTime1(S)
Level 1 Min. grid trip
voltage
0.00
2.00
655.00
0.00
2.00
655.00
GridVoltMin2
(%)
Level 2 Min. grid voltage
30.00
60.00
100.00
30.00
60.00
100.00
VoltMinTripTime2(S)
Level 2 Min. grid trip
voltage
0.00
1.00
655.00
0.00
1.00
655.00
GridVoltMin3
(%)
Level 3 Min. grid voltage
30.00
45.00
100.00
30.00
45.00
100.00
VoltMinTripTime3(S)
Level 3 Min. grid trip
voltage
0.00
0.16
655.00
0.00
0.16
655.00