EasyManua.ls Logo

CPS SCA36KTL-DO/US-480 - Page 108

CPS SCA36KTL-DO/US-480
156 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
101
Table 6-8 Reactive Power Control (IEEE-1547, Rule21, and ISO-NE)
Grid Reactive Power Derating
Setting Range
Parameter
Name
Description
IEEE1547-2018
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min
Default
Max
CtrMode
The control mode of
reactive power
0: Disable dispatch mode.
1: Remote dispatch mode.
2: Local control, by Q
3: Local control, by PF
4: PF(P) curve
5: Q(U) curve
6:Q(P)curve
0
3
6
0
5
6
0
0
6
Percentage
(%)
Local Power Factor
Setting
-60
0
60
-60
0
60
-60
0
60
PFSetValue
Local Power Factor
Setting
-1.0,
-0.8
1.0
0.8,
1.0
-1.0,
-0.8
-0.95
0.8,
1.0
-1.0,
-0.8
1.0
0.8,
1.0
ReactivePowerO
ver
Reactive power over-
provisioning enable
setting
0: Disable
1: Enable
0
0
1
0
0
1
0
0
1
PFCurveP1
%
Power of PF(P) Curve
point 1
0
50
110
0
50
110
0
50
110
PFpCurvePF1
PF of PF(P) Curve point 1
-1.0,
- 0.8
1.0
0.8,
1.0
-1.0,
- 0.8
1.0
0.8,
1.0
-1.0,
- 0.8
1.0
0.8,
1.0
PFCurveP2
%
Power of PF(P) Curve
point 2
0
100
110
0
100
110
0
100
110
PFpCurvePF2
PF of PF(P) Curve point 2
-1.0,
- 0.8
-0.9
0.8,
1.0
-1.0,
- 0.8
-0.9
0.8,
1.0
-1.0,
- 0.8
-0.9
0.8,
1.0
PFCurveTriVol
(%)
The trigger voltage of
PF(P)Curve
100
100
110
100
100
110
100
100
110
PFCurveUndoV
ol (%)
PF curve revocation
voltage
90
90
100
90
90
100
90
90
100

Table of Contents

Related product manuals