102
Note: The PF and Q value can be adjusted by remote software if the
“Remote” setting is selected.
1. PFSetValueSet the PF value. This function changes the reactive
power by adjusting the Power Factor.
2. PFpCurve functionsPFp curve mode. Using the curves to set
the PFp setpoints (See Figure 6-16).
PF
(P%)
1
(PFCurveP1,PFpCurvePF1)
(PFCurveP2,PFpCurvePF2)
Inductive
Capacitive
-1
-0.8
0.8
Figure 6-16 PF(P) Curve Mode
3. Q(U) CurveQ(U) curve mode. Using the curves to set the reactive
power setpoints (See Figure 6-17). The reactive power
compensation changes according to the grid voltage.