Page 20
Option 1
Invert Output
- This option is used to invert the normal state of the output. The PW16 uses open
collector type transistor switches and the default state of all outputs is off or high. When in alarm the
transistor switch is turned on and the output is switched low. The invert option reverses this function.
Option 2
Flash Output
- This option causes the output to switch on and off at a rate set by the pulse timer for the
output when in alarm and is normally used to flash a lamp during an activation.
Option 3
Single Pulse to Output
- This option, when applied, produces a single pulse set by the pulse timer at
the output during an alarm.
Option 4
Lockout Once Reset
- This option is used to limit the output to one operation per arming period.
Option 5 Output mapped to Remote Command Control - This option is used to map an output to the remote
command control function whereby the output can be controlled via the telephone (this requires the
optional voice board or DTMF unit)
Option 6 Output mapped to Local Command Control - This option is used to map an output to the local
command control feature whereby the output can be controlled directly from the keypad. The DTMF
command control code at address P371 is used for this local control function.
Option 7
Day Zones Linked to Pulse Timer
- Day Zones programmed to this output will pulse at the rate
programmed for the pulse timer to this output for the duration of the day zone to Output timer (e.g. if the
day zone is in partition A, then the timer at P571E applies)
Option 8
Pulsed 24 hour alarm
- If a 24 hour zone activates the alarm this option will cause the output to pulse
at a rate equal to the value set for the pulse timer for this output. This feature is provided to differentiate
between a burglar and fire alarm using the same siren.
P202E - P208E
As per P201E above for Outputs 2-8
PRIMARY ALARMS TO OUTPUT OPTIONS
P211E - P218E
In this block of addresses P211E relates to output #1, P212E relates to output #2 etc
P211E 1E Keypad Panic Alarm to Output #1
2E Keypad Fire Alarm to Output #1
3E Keypad Medical Alarm to Output #1
4E Duress Alarm to Output #1
5E Wrong Code Tamper Alarm to Output #1
6E Radio Key Panic Alarm to Output #1
7E 24 Hour Zone Alarm to Output #1
8E 24 Hour Fire Zone Alarm to Output #1
Option 1 Keypad Panic to Output - This option is used to map the operation of the keypad panic button to an
output i.e. when the Panic button (or 1 & 3) on a keypad is pressed any output with this option enabled
will turn on.
Option 2 Keypad Fire Alarm to Output - This option is used to map the operation of the keypad Fire Alarm
(buttons 4 & 6) to an output i.e. when the Fire Alarm (4 & 6) on a keypad is pressed any output with this
option enabled will turn on.
Option 3
Keypad Medical Alarm to Output
- This option is used to map the operation of the keypad Medical
Alarm (buttons 7 & 9) to an output i.e. when the Medical Alarm (7 & 9) on a keypad is pressed any
output with this option enabled will turn on.
Option 4 Duress Alarm to Output - This option is used to map a Duress Alarm to an output. A Duress Alarm is
generated when the alarm is unset by a valid user that adds the duress digit to the beginning of their
code
Option 5 Wrong Code Tamper Alarm to Output - This option is used to map the Wrong Code Tamper Alarm
to an output. A Wrong Code Tamper Alarm is generated if an invalid code is entered more than 4 times
Out 1 Option B
- - - - - - 7 8