OPTIONS “B”
KEY-SWITCH and TAMPER OPTIONS
- P311E
P311E 1E Cabinet tamper is loop or end-of-line
2E Key-switch input is loop or end-of-line
3E Low Key-switch is momentary or latching
4E High Key-switch is momentary or latching
5E Spare
6E Spare
7E Spare
8E Spare
Option 1
Cabinet tamper is loop or end-of-line
- This option determines if the Cabinet tamper input
uses a closed loop or 2k2 end-of-line resistor. If this option is on the tamper is a 2k2.
Option 2 Cabinet tamper is loop or end-of-line - This option determines if the Cabinet tamper input
uses a closed loop or 2k2 end-of-line resistor. If this option is on the tamper is a 2k2.
Option 3 Low Key-switch is momentary or latching - This option determines if the low Key-switch (4k7)
is momentary or latching. If option 3 is on the low Key-switch will be momentary
Option 4 High Key-switch is momentary or latching - This option determines if the high Key-switch
(8k2) is momentary or latching. If option 4 is on the
high Key-switch will be momentary
PROGRAMMING DURESS DIGIT
P350E
P350E 0-9
Duress Digit
(Default 0) - A Duress Alarm is activated only when the "Duress Digit" defined at
this address is prefixed to a valid user code. The resulting Duress Alarm will unset the Area in
the normal way, operate an output if one is defined and report a duress event via the
communicator. Values of 0-9 may be entered at this address where 0 = option disabled and 1-9
represent valid digits 1-9.
SETTING ZONE RESPONSE
TIME
P420E
Zone Response Time Setting - 1-31E. Default = 6
The input response count sets the total time the zones must be in alarm before the state is recognised by the panel.
A count of 1 = 45ms. The default setting of 6 therefore results in a zone response time of 270ms.
SETTING ZONE VIBRATION SENSITIVITY
P411E - P418E
Duress Digit
0
Zone Response se
6