Contact ID Reporting Code Summary
In addition to the programmable Contact ID Event Code assignments defined at P157E, P158E, P159E, P175E (9E-11E) there
are a number of fixed event codes. The programmable and fixed event codes are all listed in the table below. Associated with the
fixed and programmable event codes, there are a number of extension codes, that are also listed below. The list of extension
codes is for your reference only and can not be changed in programming. For “Users” Above 998 the panel will report all as user
998 (eg users 998-2000 will all be reported as 998).
Event Type Event Code Extension Comment
System Tamper 137 000 Panel & Sat Tamper etc
Zone Alarm (wired or wireless) 130 001 to 064 Alarm on Zone 1-64
Zone Tamper - Low (short circuit) 383 001 to 064 Zone Input 1-64 short circuit
Zone Tamper - High (open circuit) 383 009 to 064 Zone Input 1-32 open circuit
Zone Tamper - Radio Zone 383 001 to 064 Radio Zone 1-64
Zone Near Alarm 138 001 to 064 Zone Input 1-64
Zone Confirmed Alarm 139 001 to 064 Zone Input 1-64
Radio PIR / Reed Switch Battery Low 384 001 to 064 Radio Zone 1-64
Radio PIR Supervised Alarm 381 001 to 064 Supervised Radio Zone 1-64
Sensor-watch Alarm 391 001 to 064 Zone 1-64
Zone Excludes 570 001 to 064 Exclude Zone 1-64
Keypad Panic (or CONTROL+CHIME) 120 001 to 032 Panic at keypad #1-32
Radio-Key Panic 120 101 to 998 Panic by Radio User # 101-2000
Keypad Fire (A+B) 110 001 to 032 Fire Alarm at keypad #1-32
Keypad Medical (B+CHIME) 100 001 to 032 Medical Alarm at keypad #1-32
Keypad Tamper Switch Alarm 137 001 to 032 Keypad 1-32 Tamper Switch Activated
Wrong Code Alarm 461 001 to 032 4 Incorrect code entries at KP # 1-32
Arm/Disarm by "ARM key (Quick Arm) 408 000 Arm/Disarm by single button
Arm/Disarm by user code 401 001 to 998 Arm/Disarm by User #1-2000
Arm/Disarm by Radio-key 400 101 to 998 Arm/Disarm by Radio User #101-2000
Arm/Disarm by Key-switch 409 001 to 064 Zone Key-switch # 1-64 Arm/Disarm
Arm/Disarm by DTMF or Up/Download 407 000 Remote Arm/Disarm
Arm by “Security Interlock” Zone 407 001 to 064 Arm by “Security Interlock” zone # 1-64
Arm/Disarm by Time-Zone 403 000 Time-Zone Arm/Disarm
Latchkey Disarm 642 001 to 998 Latchkey User Disarm
Fail to Arm on Time-Zone 455 000 Auto Arm fail
Delinquency Alarm 454 000 System not Armed within # days
Stay Mode Arm/Disarm (part set) 441 000 Arm by “Stay” Button
Stay Mode Arm/Disarm (part set) 441 001 to 998 Stay Mode Arm by User # 1-2000
Stay Mode Arm/Disarm by Key-switch 442 000 to 064 Stay Mode Arm by Zone Key-switch # 1-64
AC Fail 301 000 Mains (AC) fail
Zone Expander AC Fail 301 001-007 AC Fail on Zone exp. 1-7
Output Expander AC Fail 301 101-108 AC Fail on Output exp. 1-8
Wiegand Interface AC Fail 301 201-232 AC Fail on Wiegand IF 1-32
System Battery Low 302 000 Control Panel Battery low
Zone Expander Battery Low 302 001-007 Battery Low on Zone exp. 1-7
Output Expander Battery Low 302 101-108 Battery Low on Output exp. 1-8
Wiegand Interface Battery Low 302 201-232 Battery Low on Wiegand IF 1-32
Checksum Fail (Corrupt EEPROM Data) 303 001-008 Checksum block error
Fuse Fail 312 000 Fuse 1 or 2 Fail
Radio-key Battery Low 384 101 to 998 Radio-key User #101-2000 low batt.
Radio-PIR / Reed Switch Battery Low 384 001 to 064 Radio Zone 1-64
Automatic TEST Calls 602 000 24 hour test
Manual TEST Calls 601 000 User generated Test Call
Phone Line Failure 351 000 Reported when line is restored
IP Communication Failure 351 002 Reported when IP Comms restore
Duress Alarm 121 001 to 032 Duress at Keypad #1-32
Program Mode Entry 627 000 Program Mode entered
Program Mode Exit 628 000 Program Mode exited
Zone Expander Tamper Alarm 145 001-007 Zone expander board Tamper Alarm
Output Expander Tamper Alarm 341 001-008 Output expander board Tamper Alarm
Wiegand IF-2 Tamper Alarm 137 001-032 Wiegand IF-2 board Tamper Alarm
Zone Expander Module Fail 333 001-007 Zone exp. 1-7 Fail
Output Expander Module Fail 333 101-108 Output exp. 1-8 Fail
Wiegand Interface Module Fail 333 201-232 Wiegand IF 1-32 fail