Page 55
GLOBAL ZONE EOL (End-of-Line) OPTIONS - P119E 1E Value 1-16
(If the Value is set to 0 the individual options can be selected at program location P125E)
Option 1 - 1k Option 9 - 10k
Option 2 - 1k5 Option 10 - 12k
Option 3 - 2k2 Option 11 - 22k
Option 4 - 3k3 Option 12 - 2k2 in series with 4k7 (Single Zone with tamper)
Option 5 - 3k9 Option 13 - 3k3 in series with 6k8 (Single Zone with tamper)
Option 6 - 4k7 Option 14 - 2k2 in series with 4k7 & 8k2 (Zone doubling with tamper)
Option 7 - 5k6 Option 15 - 4k7 in series with 8k2 (Zone doubling no tamper)
Option 8 - 6k8 Option 16 - 4k7 in parallel with 8k2 (Zone doubling no tamper)
ZONE KEYSWITCH PROGRAMMING
KEY-SWITCH ACCESS & OPERATIONAL OPTIONS - P120E 1-64E A zone can become a key-switch.
Option 1 - Key-Switch can Arm
Option 2 - Key-Switch can Arm Stay Mode
Option 3 - Key-Switch can Disarm
Option 4 - Key-Switch can Disarm Stay Mode
Option 5 - Key-Switch has Security Guard Options
Option 6 - Key-Switch will Arm Latchkey Mode
Option 7 - Key-Switch is NO (Normally Open)
Option 8 - Key-Switch is Momentary
Option 1 Key-Switch can Arm - This option enables Arming of the assigned Area via the Key-switch function
assigned to the selected zone.
Option 2 Key-Switch can Arm Stay Mode - This option enables Stay Mode Arming of the assigned Area via the
Key-switch function assigned to the selected zone.
Option 3 Key-Switch can Disarm - This option enables Disarming of the assigned Area via the Key-switch
function assigned to the selected zone.
Option 4 Key-Switch can Disarm Stay Mode - This option enables Stay Mode Disarming of the assigned Area
via the Key-switch function assigned to the selected zone.
Option 5 Key-Switch has Security Guard Options - If the zone with the key-switch function assigned has option
5 on, they can Arm all Areas assigned, but they may only Disarm if the panel is currently Armed and in
the alarm state.
Option 6 Key-Switch will Arm Latchkey Mode - If the panel is armed by a zone with the key-switch function
assigned with this option on, then the panel will be armed in Latchkey mode. This means that when the
alarm is disarmed by a key-switch with this option off, or a code with option 6 at P4E off, then a disarm
report will be sent. The option is designed to alert the alarm owner when children have returned home
and disarmed the alarm.
Option 7 Key-Switch is NO (Normally Open) - The key-switch can be a NO (Normally Open) or a NC (Normally
Closed) key-switch. The normal, or rest state, of the key-switch can be programmed at this location. If
the key-switch contacts usually rest in the open state and close when the key-switch is operated you
should turn on option 7.
Option 8 Key-Switch is Momentary - The operation of the key-switch can be momentary or latching. If option 8
is on, the key-switch operation is assumed to be momentary. This means that each time the key-switch
is operated then released the area will toggle its current state (ie if armed it will become disarmed or vice
versa). If this option is turned off it is assumed that the key-switch is a latching type. This means that
when the key-switch is operated and the key removed the contacts remain in the same state. When a
latching key-switch is used, turning on the switch will arm the area and turning it off will disarm the area.
ZONE AREA ASSIGNMENT
ZONE AREA ASSIGNMENT - P121E 1-64E Value = 01-32 for Areas 1-32
Option 01 = Zone is assigned to Area 1 - Option 32 = Zone is assigned to Area 32
Option 01 Area ā1ā - This option assigns the Zone to Area 1. If a Zone is assigned only to Area 1 it will activate if
Area 1 is armed. If the zone is in more than one Area and option 6 is OFF at address P123E then the