Code/Tag/Radio User End Time
P1029E 1-2000E - HH:MM The time a Code/Tag will cease to function.
If an access Code, Tag/Card or Radio User has an end time programmed at this address the user will only be
able to be used up to the end time at which time it will stop working. If an end time of 09:59 was programmed the
user will work until the end of the 59th minute (eg the user will work up to 10:00). If a value of 00:00 is
programmed the end time is ignored.
+++++Miscellaneous Panel & Clock Settings+++++
INSTALLER CODE
INSTALLER CODE - P25E 1E
This code is used to enter full Installer Program mode. The default installer code is 000000. This code can only be
changed while in Installer Program Mode. To enter your new installer code press P25E1E. The existing code will
be displayed at the keypad (either each digit flashed out sequentially on an ICON LCD keypad or shown on the
bottom line of the FULL LCD keypad). To change the code simply enter the digits of the new code followed by
ENTER and it will replace the old one. The Installer Code must be between 4-6 digits in length.
DURESS DIGIT
DURESS DIGIT - P25E 2E (Value can be 1-9, 0 = Duress Disabled)
The duress digit can be a number from 1-9 (a value of 0 means the duress function is disabled).
To create a duress alarm the duress digit must be entered before a valid user code (eg If the code was 123 and
the duress number was 4, then entering a code of <4123> <ENTER> would create a duress alarm).
DIAL REPORT DELAY
DIAL REPORT DELAY - P25E 3E (0-255 Seconds)
If this address is set to 0, there will be no report delay. If it is set to any value other than 0 then a delay equal to
the programmed value will stop the panel from reporting an alarm until this delay time expires. If there is a delay
programmed and the alarm is Disarmed before the delay expires no activations will be sent.
RADIO ZONE SUPERVISED TIMER
RADIO ZONE SUPERVISED TIMER - P25E 4E (Value 0-9999 Minutes)
If a radio detector is capable of sending regular supervisory signals to the panel and the zone type is set for
Supervised Signal Active, this timer sets how long a period has to elapse with no received transmissions before
a supervisory failure alarm is generated.
TWO TRIGGER TIMER
TWO TRIGGER TIMER - P25E 5E (0-255 Seconds)
If a zone is set to two trigger, the zone has to cause an alarm twice within the two trigger time period to cause an
alarm. If multiple zones are set to two trigger, an alarm will be generated if two zones trigger once each within the
two trigger time period. If a two trigger zone goes into alarm but remains in alarm for longer than the two trigger
time period (ie detector failure or cable cut) an alarm will be generated.
MAINS FAIL REPORTING DELAY
MAINS FAIL REPORTING DELAY - P25E 6E (0-9999 Seconds)
If a Mains Failure occurs this timer delays the reporting of Mains Failure to a Monitoring Station. If the mains
power returns before the timer expires then no report is sent. If Mains Failure is assigned to an output, this delay
must expire before the output will turn on.
RECEIVER FAIL DELAY
RECEIVER FAIL DELAY - P25E 7E (0-9999 Seconds)