Loading...
^ Operation
VA 500 Bi-directional English 1.24 Seite 41 von 56
11.3.2.3 Modbus Settings Register 
Modbus
Register
Register
Address
No.of
Byte
Data
Type
Description
Default
Setting
Read
Write
Unit /Comment
2001
2000
2
UInt16
Modbus ID
1
R/W
Modbus ID 1…247
2002
2001
2
UInt16
Baudrate
4
R/W
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200
5 = 38400
6 = 57600
7 = 115200
2003
2002
2
UInt16
Parity
1
R/W
0 = none
1 = even
2 = odd
2004
2003
2
UInt16
Number of Stopbits
R/W
0 = 1 Stop Bit
1 = 2 Stop Bit
2005
2004
2
UInt16
Word Order
0xABCD
R/W
0xABCD = Big Endian
0xCDAB = Middle Endian