Si33-105 Test Operation
Test Operation R407C PLUS Series Heat Recovery System 125
1.11.2 Emergency Operation:
Set in setting mode 2. Operates the system when an outdoor unit malfunctions.
1. When an inverter type outdoor unit malfunctions
When an inverter type compressor malfunctions, you can continue operation using constant
speed type compressors only.
Emergency Operation Method
1. Set to “EMG” in setting mode 2.
and
2. All indoor units connected to this outdoor unit are turned on by thermostat.
Emergency operation stops at the following conditions.
1. Emergency operation mode is reset on outdoor unit PC board.
or
2. One or more indoor units connected to this outdoor unit are turned off by thermostat.
Setting of Emergency Mode
Setting Method LED Display
H1P H2P H3P H4P H5P H6P H7P
Hold down the Mode button for 5 seconds to change to
setting Mode 2.
8777777
Push SET button and select LED display to “Emergency
Mode”.
8777777
Push the RETURN button. 8777779
Push SET button and select LED display as shown right. 8777797
Push the RETURN button to enter “Emergency Mode”.
All indoor units must be thermostat ON.
8777787