Specifications Si33-105
12 Specifications R407C PLUS Series Heat Recovery System
1.2 BS unit
Notes:
"
1 If the total capacity of all indoor units connected to the system is less than 5.6kW, connect the attached
pipe to the field pipe.
(Braze the connection between the attached pipe and field pipe.)
"
2 Use the field flanged pipe.
Also, with a 250 class indoor unit, connect the attached reducer to the field pipe.
(Braze the connection between the attached pipe and field pipe.)
Model BSVP100KJV1 BSVP160KJV1 BSVP250KJV1
Power Supply 1 Phase 50Hz 220~240V 1 Phase 50Hz 220~240V 1 Phase 50Hz 220~240V
Casing Galvanized steel plate Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 185×310×280 185×310×280 185×590×435
Sound absorbing thermal insulation material
Flame and heat resistant foamed
polyethyrene
Flame and heat resistant foamed
polyethyrene
Flame and heat resistant foamed
polyethyrene
Connecting
pipes
Indoor unit
Liquid pipes 9.5mm C1220T (flare connection)
"
1 9.5mm C1220T (flare connection) 12.7mm C1220T (flare connection)
Gas pipes 15.9mm C1220T (flare connection)
"
1 19.1mm C1220T (flare connection) 25.4mm C1220T (flare connection)
"
2
Outdoor
unit
Liquid pipes 9.5mm C1220T (flare connection)
"
1 9.5mm C1220T (flare connection) 12.7mm C1220T (flare connection)
Suction gas pipes 15.9mm C1220T (flare connection)
"
1 19.1mm C1220T (flare connection) 25.4mm C1220T (flare connection)
"
2
Discharge gas pipes 12.7mm C1220T (flare connection)
"
1 15.9mm C1220T (flare connection) 19.1mm C1220T (flare connection)
Weight kg 9 11 25
Standard Accessories
Installation manual, Attached pipe
Insulation for fitting, Clamps
Installation manual,
Insulation for fitting, Clamps
Installation manual, Attached pipe
Clamps