Si33-105 Test Operation
Test Operation R407C PLUS Series Heat Recovery System 135
Do not select “timer operation possible by remote controllerif not using a remote controller.
Operation by timer is impossible in this case.
"
1. Factory setting
Control mode Control by remote controller Control
mode
Operation OFF Temperatur
e control
Operation
mode
setting
Unified operation,
individual operation by
central remote controller,
or operation controlled by
timer
Unified OFF, individual
stop by central remote
controller, or timer stop
ON/OFF control
impossible by
remote controller
Rejection (Example) Rejection (Example) Rejection
(Example)
Rejection Acceptance 0
Rejection 10
Acceptance
(Example)
Acceptance
(Example)
1
(Example)
Rejection 11
OFF control only
possible by
remote controller
Acceptance Rejection Acceptance 2
Rejection 12
Acceptance Acceptance 3
Rejection 13
Centralized Acceptance Rejection Acceptance 4
Rejection 14
Acceptance Acceptance 5
Rejection 15
Individual Acceptance Rejection Acceptance 6
Rejection 16
Acceptance Acceptance 7 "1
Rejection 17
Timer operation
possible by
remote controller
Acceptance
(During timer at ON
position only)
Acceptance
(During timer at ON
position only)
Rejection Acceptance 8
Rejection 18
Acceptance Acceptance 9
Rejection 19