EasyManua.ls Logo

Daikin R407C PLUS - Page 57

Daikin R407C PLUS
267 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Safety Device and Function Parts Setting Value Si33-105
46 Function R407C PLUS Series Heat Recovery System
Parts Name
Symbol
Model
Remark
FXYKP
25KV1
FXYKP
32KV1
FXYKP
40KV1
FXYKP
63KV1
Remote
Controller
Wired Remote
Controller
BRC1A51 Option
Motors
Fan Motor M1F
AC 220~240V 50Hz
1
φ
15W 4P 1
φ
20W 4P 1
φ
45W 4P
Thermal Fuse 146°C
Thermal protector 120°C : OFF 105°C :
ON
Motor for Drain Pump M1P
AC 220-240V (50Hz)
Thermal Fuse 145°C
Swing Motor M1S
MT8-L[3PA07312-1]
AC200~240V
Thermistors
Thermistor (Suction Air)
R1T
ST8601-13
φ
4 L630
20k
(25°C)
Thermistor (for Heat
Exchanger High Temp.)
R3T
ST8605-7
φ
8 L1600
20k
(25°C)
Thermistor (Heat
Exchanger)
R2T
ST8602A-7
φ
6 L1600
20k
(25°C)
Others
Float Switch 33H FS-0211
Fuse F1U 250V 5A
φ
5.2
Transformer T1R TR22M21R8
Parts Name Symbol
Model
Remark
FXYSP
20KV1
FXYSP
25KV1
FXYSP
32KV1
FXYSP
40KV1
FXYSP
50KV1
FXYSP
63KV1
FXYSP
80KV1
FXYSP
100KV1
FXYSP
125KV1
Remote
Controller
Wired Remote
Controller
BRC1A52 Option
Motors
Fan Motor M1F
AC 220~240V 50Hz
1
φ
50W 1
φ
65W 1
φ
85W
1
φ
125
W
1
φ
135W
1
φ
225
W
Thermal Fuse 152°C
Thermal protector
135°C : OFF 87°C : ON
Motor for Drain Pump M1P
AC220-240V (50Hz)
Thermal Fuse 169°C
Thermistors
Thermistor (Suction Air)
R1T
ST8601-4
φ
4 L800
20k
(25°C)
Thermistor (for Heat
Exchanger High Temp.)
R3T
ST8605-7
φ
8 L1600
20k
(25°C)
Thermistor (Heat
Exchanger)
R2T
ST8602-6
φ
6 L1250
20k
(25°C)
Others
Float Switch 33H FS-0211
Fuse F1U 250V 10A
φ
5.2
Thermal Fuse TFu 109°C 10A
Transformer T1R TR22M21R8