Outline of Control (Outdoor Unit) < Symbols using in this manual > Si33-105
66 Function R407C PLUS Series Heat Recovery System
Compressor Operation Steps
The operating frequency changes in the following steps.
!
RSEYP16K~20K
!
RSEYP24K~30K
NO.
Frequency
NO.
Frequency
INV STD INV STD1 STD2
129HzOFF 129HzOFF OFF
231HzOFF 231HzOFF OFF
333HzOFF 333HzOFF OFF
435HzOFF 435HzOFF OFF
537HzOFF 537HzOFF OFF
639HzOFF 639HzOFF OFF
741HzOFF 741HzOFF OFF
843HzOFF 843HzOFF OFF
946HzOFF 946HzOFF OFF
10 48Hz OFF 10 48Hz OFF OFF
11 52Hz OFF 11 52Hz OFF OFF
12 55Hz OFF 12 55Hz OFF OFF
13 58Hz OFF 13 58Hz OFF OFF
14 62Hz OFF 14 62Hz OFF OFF
15 64Hz OFF 15 64Hz OFF OFF
16 67Hz OFF 16 67Hz OFF OFF
17 71Hz OFF 17 71Hz OFF OFF
18 75Hz OFF 18 75Hz OFF OFF
19 37Hz ON 19 37Hz ON OFF
20 41Hz ON 20 41Hz ON OFF
21 46Hz ON 21 46Hz ON OFF
22 52Hz ON 22 52Hz ON OFF
23 58Hz ON 23 58Hz ON OFF
24 64Hz ON 24 64Hz ON OFF
25 71Hz ON 25 71Hz ON OFF
26 79Hz ON
16 HP upper
limit
26 41Hz ON ON
27 87Hz ON 27 52Hz ON ON
28 95Hz ON
18, 20 HP
upper limit
28 64Hz ON ON
29 79Hz ON ON
24, 26 HP
upper limit
30 87Hz ON ON
31 95Hz ON ON
28, 30 HP
upper limit