Troubleshooting for Indoor Unit SiUS12-928_B
149 Service Diagnosis
Troubleshooting
Check No.01
Refer to P.191
NO
NO
NO
Check No. 01
Check the indoor heat exchanger
thermistor.
YES
YES
(R15715)
YES
YES
NO
Caution
Provide sufficient air passage.
Clean the air filter.
Clean the indoor heat
exchanger.
Replace the indoor unit PCB.
Replace the thermistor.
As described in the
thermistor characteristic
chart?
Check the air filter.
Check the dust accumulation on
the indoor heat exchanger.
Is there any short circuit?
Dirty?
Dirty?
Check the air passage.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.