AKC ON (Evap shutdown when injection o)
One of the main features of the AKC On function is that the SM 
will detect if there is a pack shutdown condition.  The SM does 
this by monitoring the pack controller for such conditions.  If 
congured to do so, and upon detecting a pack shut down, the 
SM will issue a signal to all (congured) evap controllers under the 
pack suction group to close their AKV valves.  The eect of closing 
the local AKV valve is to limit liquid ow in the evaporator.  Due 
to the AKV valve being closed during a pack shutdown period 
there is a greatly reduced risk of liquid hammer or compressor 
damage upon pack / compressor start up.  The AKC ON function 
must be congured for each pack suction group.  By default, the 
associated evap controllers are set to ‘yes’ under the selection 
choice of Evap shutdown when injection o.  If a evap controller is 
not required to be part of the suction group AKC ON function, set 
this value to ‘No’. 
Pack Conguration
Under the settings / Summary screen set the question
Evap shutdown when injection o to ‘YES’
Evap Conguration
If the Evap is not required to be part of the AKC ON function, modify 
the question
Evap shutdown when injection o to ‘No’