Demand Limiting
The AK-SM Demand Limiting function is based on a designated 
utility power meter.  Only one meter can be assigned Demand 
limiting, even though  up to 80 meters can be connected to the 
AK-SM.  Once a meter has been selected, the Demand Limit func-
tion can be applied against any Lighting and HVAC load.
Utility demand is monitored every minute.  Every minute, the 
most recent n minutes are averaged (where n is the width of the 
congured window, 15, 20, or 30 minutes dened in the meter 
set up window Conguration->Control->Energy).  If the average 
reaches the congured “start shedding at” percentage of cong-
ured maximum demand, Step one (all lighting zones and HVAC 
units assigned to level 1) will be turned o.  After one minute, 
when the average is calculated again, if the demand is still above 
the congured percentage of congured maximum demand, level 
two will be shed, and so on.  When demand has dropped to the  
“start restoring at” level, the last level shed will be restored, and 
then the others in descending order, so that the last load restored 
will be the one which was shed rst. 
Restoration will continue as long as the load remains below the 
“start shedding at” percentage.
If both normal and emergency load limits are to be established,  
the relative on/o input for the automatic transfer switch must 
be wired and congured.  In addition, if the site has a coupling 
switch, you must wire and congure an on/o input for the cou-
pling switch.
 
Priority Levels (normal conditions)
Levels are shed in ascending order: level 1, then level 2, and so on 
up to the highest level congured, limited by the number of steps
allowed.  Levels above the number of steps congured will not be 
shed unless the meter conguration is changed  (Conguration-
>Control->Energy meter setup).  Since there are only up to ten 
steps, loads assigned level 11 will never be shed.  It is recom-
mended that loads which are not to be shed are left at level 11, 
the default value.
 
Enter the required Shed levels & Emergency 
levels for the HVAC & Lighting systems.
Emergency level 
The priority for shedding when the emergency generator is 
running.  If a load is assigned level 0 (zero) for either normal or 
emergency 
conditions, the load will never come on under those conditions.
Conguration->Control->Energy Demand Limiting
As previously mentioned the Demand Limiting function is applied 
against HVAC and Lighting loads.  This example assumes that both 
HVAC and lighting have been dened in the AK-SM and that a 
meter has been selected for Demand Limiting.
Navigate to the Demand Limiting tab.  The HVAC and lighting 
systems will be seen in this page, allowing the conguration of 
shed levels.
62  User Guide  Lit. no. USCO.PI.R1.E1.02 © Danfoss 07-2013  AK-SM 850