EasyManua.ls Logo

Danfoss AK-SM 850 - Page 53

Danfoss AK-SM 850
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Zone Name: Custom description (User Def) or select from a drop
down list
User Dened Name: Enter required name
Photocell: None (no photocell), Inside photocell, Outside
photocell or Skylight
Control Sensor: Min: The lowest-reading photocell at any given
time will be used as the control sensor. Max: The highest-reading
photocell at any given time will be used as the control sensor.
Average: All photocells are averaged, and the average value is
used as the control sensor value. Photocell ID#1 (etc.): If any
specic photocell is selected , its value alone will be used as the
control sensor value.
Num of Schedules: The number of schedules for this point.
Control Method: Schd and photo: For this point to be on, two
conditions have to be satised: (1) the schedule must be true; and
(2) the photocell must be above trip level. Once those two
conditions are satised, the pre-delay timer will start. Schd or
photo: For this point to be on, either of two conditions must be
satised: (1) the schedule must be true; or (2) the photocell must
be above trip level. Once one of those two conditions is satised,
the pre-delay timer will start.
Tip! For outside lighting control via photocell, the light level needs
to be below the trip level. In the case of interior lighting, turn o
lights when we’re above a trip level.
Num of control relays: Each zone is controlled by a relay output
(digital output) on the I/O network.
Trip Level %: The % level at which the photocell condition will be
true and act to turn the lights on. (If multiple relays are congured,
there will be one trip level per relay.)
Range: +/-: The range selected creates a dead band.
Pre Delay: When lights are o, the number of minutes that the
lighting condition must be satised before lights will be turned
on.
Post Delay: When lights are on, the number of minutes that the
lighting condition must be false before lights will be turned o.
Minimum on Time: When lights are turned on, the number of
minutes that they must remain on before being turned o.
Minimum o Time: When lights are turned o, the number of
minutes that they must remain o before being turned on.
Override Switch: (Yes / No) Whether or not there is an override
switch assigned to the zone.
Override Duration: The duration of an override when the
override switch is used.
Burglar Override: When this zone’s lights are turned o, whether
they are to be turned on when a monitored burglar alarm is
sensed.
Fire Override: When this zone’s lights are turned o, whether
they are to be turned on when a monitored re alarm is sensed.
There is no pre-delay for re alarms.
Enable Dimmer output: Whether or not a dimmer variable
output will be controlled.
Target %: The photocell level that the controller will seek to
maintain by operation of the dimmer.
Minimum output (0.0v): The minimum dimmer level.
Maximum output (10.0v): The maximum dimmer level.
Algorithm sensitivity:
Algorithm interval:
Max rate of change (% / Sec):
Tip! Target % applies if ‘inside’ or ‘outside’ photocell used. If a
skylight photocell used, then the min output/max output (slope
between 2 points) approach is enabled.
Schedules:
Type 1: Standard (directly linked with AK-SC lighting sched-
ule), Relative (a time that is dened before or after the scheduled
start / stop times).
Start1: Scheduled Start time
Stop 1: Scheduled Stop time
Days 1: Days of the week that will apply to this schedule
Holidays: Holidays that will apply to this schedule
AK-SM 850 User Guide Lit. no. USCO.PI.R1.E1.02 © Danfoss 07-2013 53

Related product manuals