Recommended max. fuse
Power
[kW]
SIBA
Type RK1
Littel fuse
Type RK1
Ferraz-
Shawmut
Type CC
Ferraz-
Shawmut
Type RK1
1.1-2.2 5017906-010 KLS-R-10 ATM-R-10 A6K-10-R
3 5017906-016 KLS-R-15 ATM-R-15 A6K-15-R
4 5017906-020 KLS-R-20 ATM-R-20 A6K-20-R
5.5 5017906-025 KLS-R-25 ATM-R-25 A6K-25-R
7.5 5012406-032 KLS-R-30 ATM-R-30 A6K-30-R
11-15 5014006-040 KLS-R-40 - A6K-40-R
18 5014006-050 KLS-R-50 - A6K-50-R
22 5014006-063 KLS-R-60 - A6K-60-R
30 2028220-100 KLS-R-80 - A6K-80-R
37 2028220-125 KLS-R-100 - A6K-100-R
45 2028220-125 KLS-R-125 - A6K-125-R
55 2028220-160 KLS-R-150 - A6K-150-R
75 2028220-200 KLS-R-200 - A6K-200-R
90 2028220-250 KLS-R-250 - A6K-250-R
Table 6.27 380-500 V, Enclosure Types A, B and C
Recommended max. fuse
Power
[kW]
Bussmann
JFHR2
Ferraz- Shawmut
J
Ferraz- Shawmut
JFHR2
1)
Littel fuse
JFHR2
1.1-2.2 FWH-10 HSJ-10 - -
3 FWH-15 HSJ-15 - -
4 FWH-20 HSJ-20 - -
5.5 FWH-25 HSJ-25 - -
7.5 FWH-30 HSJ-30 - -
11-15 FWH-40 HSJ-40 - -
18 FWH-50 HSJ-50 - -
22 FWH-60 HSJ-60 - -
30 FWH-80 HSJ-80 - -
37 FWH-100 HSJ-100 - -
45 FWH-125 HSJ-125 - -
55 FWH-150 HSJ-150 - -
75 FWH-200 HSJ-200 A50-P-225 L50-S-225
90 FWH-250 HSJ-250 A50-P-250 L50-S-250
Table 6.28 380-480 V, Enclosure Types A, B and C
Electrical Installation Design Guide
MG11BC02 Danfoss A/S © Rev. 06/2014 All rights reserved. 101
6 6

Table of Contents

Other manuals for Danfoss FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 102 and is the answer not in the manual?

Danfoss FC 102 Specifications

General IconGeneral
BrandDanfoss
ModelFC 102
CategoryDC Drives
LanguageEnglish

Related product manuals