NOTICE
Unsuccessful AMA is often caused by incorrectly
registered motor name plate data, or a too big
difference between the motor power size and the
frequency converter power size.
Step 4. Set speed limit and ramp times
Set up the desired limits for speed and ramp time:
3-02 Minimum Reference.
3-03 Maximum Reference.
4-11 Motor Speed Low Limit [RPM] or 4-12 Motor
Speed Low Limit [Hz].
4-13 Motor Speed High Limit [RPM] or 4-14 Motor
Speed High Limit [Hz].
3-41 Ramp 1 Ramp Up Time.
3-42 Ramp 1 Ramp Down Time.
Electrical Installation Design Guide
MG11BC02 Danfoss A/S © Rev. 06/2014 All rights reserved. 121