Select
Initialization
[2] to reset all parameter values to default
settings, except for par. 15-03, 15-04, and 15-05. The frequency
converter will reset during the next power-up.
Par. 14-22 will also revert to the default setting
Normal opera-
tion
[0].
14-25 Trip Delay at Torque Limit
Range: Function:
60 s
*
[0 - 60 s] Enter the torque limit trip delay in seconds. When the output
torque reaches the torque limits (par. 4-16 and 4-17), a warning
is triggered. When the torque limit warning has been continu-
ously present for the period specified in this parameter, the
frequency converter trips. Disable the trip delay by setting the
parameter to 60 s = OFF. Thermal monitoring of the frequency
converter will still remain active.
14-26 Trip Delay at Inverter Fault
Range: Function:
Size re-
lated
[0 - 30 s] When the frequency converter detects an over-voltage in the
set time trip will be effected after the set time.
If value = 0,
protection mode
is disabled
NB!
It is recommended to disable
protection mode
in
hoisting applications.
14-29 Service Code
Range: Function:
000000 [000000 Hex - FFFFF] For internal service only.
FC 300 Programming Guide 2. How to Programme
MG.33.M2.02 - VLT
®
is a registered Danfoss trademark