NB!
This parameter is active only when par. 8-01
Control Site
is set to [0]
Digital and
control word
.
8-56 Preset Reference Select
Option: Function:
[0] Digital input
[1] Bus Activates Preset Reference selection via the serial communica-
tion port or fieldbus option.
[2] Logic AND Activates Preset Reference selection via the fieldbus/serial com-
munication port, AND additionally via one of the digital inputs.
[3]
*
Logic OR Activates the Preset Reference selection via the fieldbus/serial
communication port OR via one of the digital inputs.
Select control of the frequency converter Preset Reference se-
lection via the terminals (digital input) and/or via the fieldbus.
NB!
This parameter is active only when par. 8-01
Control Site
is set to [0]
Digital and
control word
.
2.11.6. 8-9* Bus Jog
Parameters for configuring the Bus Jog.
8-90 Bus Jog 1 Speed
Range: Function:
100
RPM
*
[0 - par. 4-13 RPM] Enter the jog speed. This is a fixed jog speed activated via the
serial port or fieldbus option.
8-91 Bus Jog 2 Speed
Range: Function:
200
RPM
*
[0 - par. 4-13 RPM] Enter the jog speed. This is a fixed jog speed activated via the
serial port or fieldbus option.
2.12. Parameters: Profibus
2.12.1. 9-** Profibus
Parameter group for all Profibus-specific parameters.
2. How to Programme FC 300 Programming Guide
134
MG.33.M2.02 - VLT
®
is a registered Danfoss trademark