[0 - 115] This parameter displays a list of all the frequency converter pa-
rameters deviating from default setting.
2.13. Parameters: DeviceNet CAN Fieldbus
2.13.1. 10-** DeviceNet and CAN Fieldbus
Parameter group for DeviceNet CAN fieldbus parameters.
2.13.2. 10-0* Common Settings
Parameter group for configuring common settings for CAN fieldbus options.
10-00 CAN Protocol
Option: Function:
[0] CANopen
[1]
*
DeviceNet View the active CAN protocol.
NB!
The options depend on installed option.
10-01 Baud Rate Select
Option: Function:
[16] 10 Kbps
[17] 20 Kbps
[18]
[19]
50 Kbps
100 Kbps
[20]
*
125 Kbps
[21] 250 Kbps
[22] 500 Kbps Select the fieldbus transmission speed. The selection must cor-
respond to the transmission speed of the master and the other
fieldbus nodes.
10-02 MAC ID
Range: Function:
63
*
[0 - 127] Selection of station address. Every station connected to the
same network must have an unambiguous address.
10-05 Readout Transmit Error Counter
Range: Function:
0
*
[0 - 255] View the number of CAN control transmission errors since the
last power-up.
FC 300 Programming Guide 2. How to Programme