Select which reaction the frequency converter should take in
case a fan fault is detected.
14-55 Output Filter
Option: Function:
[0]
*
No filter
[1] Sine-Wave Filter Select the type of output filter connected. This parameter can-
not be adjusted while motor is running.
14-56 Capacitance Output Filter
Range: Function:
2.0 μF
*
[0.1 - 6500.0 μF] Set the capacitance of the output filter. The value can be found
on the filter label.
NB!
This is required for correct compensation in Flux
mode (par. 1-01)
14-57 Inductance Output Filter
Range: Function:
7.000
mH
*
[0.001 - 65.000 mH] Set the inductance of the output filter. The value can be found
on the filter label.
NB!
This is required for correct compensation in Flux
mode (par. 1-01)
2.15.8. 14-7* Compatibility
This parameter is for setting of compatibility for VLT 3000, VLT 5000 to FC 300
14-72 VLT Alarm Word
Range: Function:
0
*
[0 - 4294967295] Read out the alarm word corresponding to VLT 3000 or VLT
5000
14-73 VLT Warning Word
Range: Function:
0
*
[0 - 4294967295] Read out the warning word corresponding to VLT 3000 or VLT
5000
2. How to Programme FC 300 Programming Guide
180
MG.33.M2.02 - VLT
®
is a registered Danfoss trademark
2