15-05 Over Volt's
Range: Function:
0
*
[0 - 65535] View the number of frequency converter overvoltages which
have occurred.
15-06 Reset kWh Counter
Option: Function:
[0]
*
Do not reset
[1] Reset counter Select
Reset
[1] and press [OK] to reset the kWh counter to zero
(see par 15-02).
Select
Do not reset
[0] if no reset of the kWh counter is desired.
NB!
The reset is carried out by pressing [OK].
15-07 Reset Running Hours Counter
Option: Function:
[0]
*
Do not reset
[1] Reset counter Select
Reset
[1] and press [OK] to reset the Running Hours
counter to zero (see par. 15-01). This parameter cannot be se-
lected via the serial port, RS 485.
Select
Do not reset
[0] if no reset of the Running Hours counter
is desired.
2.16.3. Data Log Settings, 15-1*
The Data Log enables continuous logging of up to 4 data sources (par. 15-10) at individual rates
(par. 15-11). A trigger event (par. 15-12) and window (par. 15-14) are used to start and stop the
logging conditionally.
15-10 Logging Source
Array [4]
None
14-72 VLT Alarm
Word
14-73 VLT Warning
Word
14-74 VLT Ext. Status
Word
[16-00
Control
Word]
16-01 Reference
[Unit]
2. How to Programme FC 300 Programming Guide
182
MG.33.M2.02 - VLT
®
is a registered Danfoss trademark
2