This parameter cannot be adjusted while the motor is running.
1-03 Torque Characteristics
Option: Function:
Select the torque characteristic required.
VT and AEO are both energy saving operations.
[0]
*
Constant torque Motor shaft output provides constant torque under variable
speed control.
[1] Variable torque Motor shaft output provides variable torque under variable
speed control. Set the variable torque level in par. 14-40
VT
Level
.
[2] Auto energy optim. Automatically optimises energy consumption by minimising
magnetisation and frequency via par. 14-41
AEO Minimum Mag-
netisation
and par. 14-42
Minimum AEO Frequency
.
This parameter cannot be adjusted while the motor is running.
1-04 Overload Mode
Option: Function:
[0]
*
High torque Allows up to 160% over torque.
[1] Normal torque For oversized motor - allows up to 110% over torque.
This parameter cannot be adjusted while the motor is running.
1-05 Local Mode Configuration
Option: Function:
Select which application configuration mode (par. 1-00), i.e. ap-
plication control principle, to use when a Local (LCP) Reference
is active. A Local Reference can be active only when par. 3-13
Reference Site
is set to [0] or [2]. By default the local reference
is active in Hand Mode only.
[0] Speed open loop
[1] Speed closed loop
[2]
*
As mode par. 1-00
2.4.2. 1-1* Motor selection
Parameter group for setting general motor data.
This parameter group cannot be adjusted while the motor is running.
1-10 Motor Construction
Option: Function:
Select the motor construction type.
[0]
*
Asynchronous For asynchronous motors.
[1] PM, non salient SPM
(FC 302 only)
For permanent magnet (PM) motors.
2. How to Programme FC 300 Programming Guide
44
MG.33.M2.02 - VLT
®
is a registered Danfoss trademark