Type designation P15K P18K P22K P30K P37K
High/normal overload
1)
HO NO HO NO HO NO HO NO HO NO
Typical shaft output [kW/(hp)]
15
(20)
18.5
(25)
18.5
(25)
22
(30)
22
(30)
30
(40)
30
(40)
37
(50)
37
(50)
45
(60)
Enclosure protection rating IP20 B4 C3 C3 C4 C4
Enclosure protection rating IP21, IP55, IP66 C1 C1 C1 C2 C2
Output current
Continuous (200–240 V) [A] 59.4 74.8 74.8 88.0 88.0 115 115 143 143 170
Intermittent (60 s overload) (200–240 V) [A] 89.1 82.3 112 96.8 132 127 173 157 215 187
Continuous kVA (208 V) [kVA] 21.4 26.9 26.9 31.7 31.7 41.4 41.4 51.5 51.5 61.2
Maximum input current
Continuous (200–240 V) [A] 54.0 68.0 68.0 80.0 80.0 104 104 130 130 154
Intermittent (60 s overload) (200–240 V) [A] 81.0 74.8 102 88.0 120 114 156 143 195 169
Additional specications
IP20 maximum cable cross-section
5)
for mains,
brake, motor, and load sharing [mm
2
] ([AWG])
35 (2) 50 (1) 50 (1) 150 (300 MCM) 150 (300 MCM)
IP21, IP55, IP66 maximum cable cross-section
5)
for mains and motor [mm
2
] ([AWG])
50 (1) 50 (1) 50 (1) 150 (300 MCM) 150 (300 MCM)
IP21, IP55, IP66 maximum cable cross-section
5)
for brake and load sharing [mm
2
] ([AWG])
50 (1) 50 (1) 50 (1) 95 (3/0) 95 (3/0)
Maximum cable cross-section
2),5)
for disconnect
[mm
2
] ([AWG])
50, 35, 35 (1, 2, 2)
95, 70, 70
(3/0, 2/0, 2/0)
185, 150, 120
(350 MCM, 300
MCM, 4/0)
Estimated power loss at rated maximum load
[W]
3)
624 737 740 845 874 1140 1143 1353 1400 1636
Eciency
4)
0.96 0.97 0.97 0.97 0.97
Table 8.3 Mains Supply 200–240 V, P15K–P37K
Specications Operating Guide
MG33AT02 Danfoss A/S © 05/2018 All rights reserved. 33
8 8