8.9 Power Ratings, Weight, and Dimensions
Enclosure size A1 A2 A3 A4 A5
Rated power
[kW (hp)]
200–240 V 0.25–1.5
(0.34–2)
0.25–2.2
(0.34–3)
3–3.7
(4–5)
0.25–2.2
(0.34–3)
0.25–3.7
(0.34–5)
380–480/500 V 0.37–1.5
(0.5–2)
0.37–4
(0.5–5)
5.5–7.5
(7.5–10)
0.37–4
(0.5–5)
0.37–7.5
(0.5–10)
525–600 V
0.75–7.5
(1–10)
0.75–7.5
(1–10)
525–690 V
1.1–7.5
(1.5–10)
IP
NEMA
20
Chassis
20
Chassis
21
Type 1
20
Chassis
21
Type 1
55/66
Type 12/4X
55/66
Type 12/4X
Height [mm (in)]
Height of mounting plate
A
1)
200
(7.9)
268
(10.6)
375
(14.8)
268
(10.6)
375
(14.8)
390
(15.4)
420
(16.5)
Height with ground termination plate for eldbus
cables
A
316
(12.4)
374
(14.7)
374
(14.7)
Distance between mounting holes a
190
(7.5)
257
(10.1)
350
(13.8)
257
(10.1)
350
(13.8)
401
(15.8)
402
(15.8)
Width [mm (in)]
Width of mounting plate B
75
(3)
90
(3.5)
90
(3.5)
130
(5.1)
130
(5.1)
200
(7.9)
242
(9.5)
Width of mounting plate with 1 C option B
130
(5.1)
130
(5.1)
170
(6.7)
170
(6.7)
242
(9.5)
Width of mounting plate with 2 C options B
150
(5.9)
150
(5.9)
190
(7.5)
190
(7.5)
242 (9.5)
Distance between mounting holes b 60 (2.4) 70 (2.8) 70 (2.8) 110 (4.3) 110 (4.3) 171 (6.7) 215 (8.5)
Depth [mm (in)]
Depth without option A/B C 207 (8.1) 205 (8.1) 207 (8.1) 205 (8.1) 207 (8.1) 175 (6.9) 200 (7.9)
With option A/B C 222 (8.7) 220 (8.7) 222 (8.7) 220 (8.7) 222 (8.7) 175 (6.9) 200 (7.9)
Screw holes [mm (in)]
c 6.0 (0.24) 8.0 (0.31) 8.0 (0.31) 8.0 (0.31) 8.0 (0.31) 8.25 (0.32) 8.25 (0.32)
d ø8 (ø0.31) ø11 (ø0.43) ø11 (ø0.43) ø11 (ø0.43) ø11 (ø0.43) ø12 (ø0.47) ø12 (ø0.47)
e ø5 (ø0.2) ø5.5 (ø0.22) ø5.5 (ø0.22) ø5.5 (ø0.22) ø5.5 (ø0.22) ø6.5 (ø0.26) ø6.5 (ø0.26)
f 5 (0.2) 9 (0.35) 9 (0.35) 6.5 (0.26) 6.5 (0.26) 6 (0.24) 9 (0.35)
Maximum weight [kg (lb)] 2.7 (6) 4.9 (10.8) 5.3 (11.7) 6.6 (14.6) 7 (15.4) 9.7 (21.4) 13.5/14.2 (30/31)
Front cover tightening torque [Nm (in-lb)]
Plastic cover (low IP) Click Click Click
Specications
VLT
®
AutomationDrive FC 301/302
56 Danfoss A/S © 05/2018 All rights reserved. MG33AT02
88

Other manuals for Danfoss FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 301 and is the answer not in the manual?

Danfoss FC 301 Specifications

General IconGeneral
TypeAC Drive
Output frequency0-1000 Hz
Enclosure ratingIP20, IP21, IP55
Control methodSensorless vector control
Communication optionsRS-485, CANopen, Profibus DP
Ambient temperature-10°C to +50°C
Supply voltage200-240 V, 380-500 V, 525-690 V
Protection classIP20, IP21, IP55
Cooling methodForced air
Relative humidity5% to 95% (non-condensing)
Storage temperature range-25 to 70 °C (-13 to 158 °F)