10.3.2 Cable and Fuse Sizes, Mains Voltage 208–240 V and 380–500 V
Table 24: Cable and Fuse Sizes, Mains Voltage 208–240 V and 380–500 V
Enclo-
sure
size
Drive type I
L
[A] Fuse
(gG/gL)
[A]
Mains, motor, and brake
resistor
(1)
cable Cu [mm
2
]
Mains terminal cable size
[mm
2
]
Grounding ter-
minal cable size
[mm
2
]
MR4 0003 2–0004 2
0003 5–0004 5
3.7–4.8
3.4–4.8
6 3x1.5+1.5 1–6 solid
1–4 stranded
1–6
0006 2–0008 2
0005 5–0008 5
6.6–8.0
5.6–8.0
10 3x1.5+1.5 1–6 solid
1–4 stranded
1–6
0011 2–0012 2
0009 5–0012 5
11.0–12.5
9.6–12.0
16 3x2.5+2.5 1–6 solid
1–4 stranded
1–6
MR5 0018 2
0016 5
18.0
16.0
20 3x6+6 1–10 Cu 1–10
0024 2
0023 5
24.0
23.0
25 3x6+6 1–10 Cu 1–10
0031 2
0031 5
31.0
31.0
32 3x10+10 1–10 Cu 1–10
MR6 0038 5 38.0 40 3x10+10 2.5–50 Cu/Al 2.5–35
0048 2
0046 5
48.0
46.0
50 3x16+16 (Cu)
3x25+16 (Al)
2.5–50 Cu/Al 2.5–35
0062 2
0061 5
62.0
61.0
63 3x25+16 (Cu)
3x35+10 (Al)
2.5–50 Cu/Al 2.5–35
MR7 0075 2
0072 5
75.0
72.0
80 3x35+16 (Cu)
3x50+16 (Al)
6–70 Cu/Al 6–70
0088 2
0087 5
88.0
87.0
100 3x35+16 (Cu)
3x70+21 (Al)
6–70 Cu/Al 6–70
0105 2
0105 5
105.0 125 3x50+25 (Cu)
3x70+21 (Al)
6–70 Cu/Al 6–70
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
106 | Danfoss A/S © 2019.05