10.3.5 Cable and Fuse Sizes, Mains Voltage 525–690 V, North America
Table 27: Cable and Fuse Sizes, Mains Voltage 525–690 V, North America
Enclosure
size
Drive type I
L
[A] Fuse (Class
T/J) [A]
Mains, motor
and brake re-
sistor
(1)
cable
Cu [AWG]
Mains terminal cable size
[AWG]
Grounding terminal cable
size [AWG]
MR5 (600
V)
0004 6 3.9 6 14 20–6 17–8
0006 6 6.1 10 14 20–6 17–8
0009 6 9.0 10 14 20–6 17–8
0011 6 11.0 15 14 20–6 17–8
MR6 0007 7 7.5 10 12 13–0 13–2
0010 7 10.0 15 12 13–0 13–2
0013 7 13.5 20 12 13–0 13–2
0018 6
0018 7
18.0 20 10 13–0 13–2
0022 6
0022 7
22.0 25 10 13–0 13–2
0027 6
0027 7
27.0 30 8 13–0 13–2
0034 6
0034 7
34.0 40 8 13–0 13–2
MR7 0041 6
0041 7
41.0 50 6 9–2/0 9–2/0
0052 6
0052 7
52.0 60 6 9–2/0 9–2/0
0062 6
0062 7
62.0 70 4 9–2/0 9–2/0
MR8 0080 6
0080 7
80.0 90 1/0 1 AWG–350 kcmil 1 AWG–350 kcmil
0100 6
0100 7
100.0 110 1/0 1 AWG–350 kcmil 1 AWG–350 kcmil
0125 6
0125 7
125.0 150 2/0 1 AWG–350 kcmil 1 AWG–350 kcmil
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 111
Danfoss A/S © 2019.05