10.6.6 Power Ratings of VACON® 100 FLOW, 380–500 V
Table 36: Power Ratings of VACON
®
100 FLOW, Mains Voltage 380–500 V, 50–60 Hz, 3~
Enclo-
sure
size
Drive type
(1)
Low loadability:
Continuous cur-
rent I
L
[A]
(2)
Low loada-
bility: Input
current I
in
[A]
(2)
Low loadabili-
ty: 10% over-
load current
[A]
(2)
Low loadabil-
ity: Max cur-
rent I
s
2 s
(2)
Motor shaft
power
(3)
: 10%
overload 40°C
[kW]
Motor shaft
power
(4)
:
10% over-
load 40°C
[hp]
MR4 0003 3.4 3.4 3.7 5.2 1.1 1.5
0004 4.8 4.6 5.3 6.8 1.5 2.0
0005 5.6 5.4 6.2 8.6 2.2 3.0
0008 8.0 8.1 8.8 11.2 3.0 4.0
0009 9.6 9.3 10.6 16.0 4.0 5.0
0012 12.0 11.3 13.2 19.2 5.5 7.5
MR5 0016 16.0 15.4 17.6 24.0 7.5 10.0
0023 23.0 21.3 25.3 32.0 11.0 15.0
0031 31.0 28.4 34.1 46.0 15.0 20.0
MR6 0038 38.0 36.7 41.8 62.0 18.5 25.0
0046 46.0 43.6 50.6 76.0 22.0 30.0
0061 61.0 58.2 67.1 92.0 30.0 40.0
MR7 0072 72.0 67.5 79.2 122.0 37.0 50.0
0087 87.0 85.3 95.7 144.0 45.0 60.0
0105 105.0 100.6 115.5 174.0 55.0 75.0
MR8 0140 140.0 139.4 154.0 210.0 75.0 100.0
0170 170.0 166.5 187.0 280.0 90.0 125.0
0205 205.0 199.6 225.5 340.0 110.0 150.0
MR9A 0261 261.0 258.0 287.1 410.0 132.0 200.0
0310 310.0 303.0 341.0 502.0 160.0 250.0
MR9B 0386 385.0 386.0 423.5 620.0 200.0 300.0
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default
2
See 10.7 Overload Capability.
3
400 V
4
480 V
If the process includes a cyclical load, for example if there are lifts or winches, speak to the manufacturer to get the dimensioning
information.
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711