Enclosure size A B C D E F G
MR8 40 180 25 300 25 300 As short as possible
MR9 40 180 25 300 25 300 As short as possible
Table 29: Cable Stripping Lengths, in inches
Enclosure size A B C D E F G
MR4 0.6 1.4 0.4 0.8 0.3 1.4 As short as possible
MR5 0.8 1.6 0.4 1.2 0.4 1.6 As short as possible
MR6 0.8 3.6 0.6 2.4 0.6 2.4 As short as possible
MR7 0.8 3.1 0.8 3.1 0.8 3.1 As short as possible
MR8 1.6 7.1 1 11.8 1 11.8 As short as possible
MR9 1.6 7.1 1 11.8 1 11.8 As short as possible
10.5 Tightening Torques of the Terminals
Table 30: Tightening Torques of the Terminals, in Nm (lb-in.)
Enclosure
size
Drive type Mains and motor terminals Grounding clamps for
cable shield
Grounding clamps for grounding
conductor
MR4 0003 2 - 0012 2
0003 5 - 0012 5
0.5–0.6 (4.5–5.3) 1.5 (13.3) 2 (17.7)
MR5 0018 2 - 0031 2
0016 5 - 0031 5
0004 6 - 0011 6
1.2–1.5 (10.6–13.3) 1.5 (13.3) 2 (17.7)
MR6 0048 2 - 0062 2
0038 5 - 0061 5
0018 6 - 0034 6
0007 7 - 0034 7
10 (88.5) 1.5 (13.3) 2 (17.7)
MR7 0075 2 - 0105 2
0072 5 - 0105 5
0041 6 - 0062 6
0041 7 - 0062 7
8
(1)
/5.6
(2)
(70.8
(1)
/49.6
(2)
)
1.5 (13.3)
8
(1)
/5.6
(2)
(70.8
(1)
/49.6
(2)
)
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 113
Danfoss A/S © 2019.05