10.6.10 Power Ratings of VACON® 100 HVAC, 380–500 V
Table 40: Power Ratings of VACON
®
100 HVAC, Mains Voltage 380–500 V, 50–60 Hz, 3~
Enclo-
sure
size
Drive type
(1)
Low Loadability:
Continuous current
I
L
[A]
(2)
Low Loadability:
Input current I
in
[A]
(2)
Low Loadabili-
ty: 10% over-
load current [A]
(2)
Motor shaft power
(3)
: 10% overload
40°C [kW]
Motor shaft
power
(3)
: 10%
overload 40°C
[hp]
MR4 0003 3.4 3.4 3.7 1.1 1.5
0004 4.8 4.6 5.3 1.5 2.0
0005 5.6 5.4 6.2 2.2 3.0
0008 8.0 8.1 8.8 3.0 5.0
0009 9.6 9.3 10.6 4.0 5.0
0012 12.0 11.3 13.2 5.5 7.5
MR5 0016 16.0 15.4 17.6 7.5 10.0
0023 23.0 21.3 25.3 11.0 15.0
0031 31.0 28.4 34.1 15.0 20.0
MR6 0038 38.0 36.7 41.8 18.5 25.0
0046 46.0 43.6 50.6 22.0 30.0
0061 61.0 58.2 67.1 30.0 40.0
MR7 0072 72.0 67.5 79.2 37.0 50.0
0087 87.0 85.3 95.7 45.0 60.0
0105 105.0 100.6 115.5 55.0 75.0
MR8 0140 140.0 139.4 154.0 75.0 100.0
0170 170.0 166.5 187.0 90.0 125.0
0205 205.0 199.6 225.5 110.0 150.0
MR9A 0261 261.0 258.0 287.1 132.0 200.0
0310 310.0 303.0 341.0 160.0 250.0
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default.
2
See 10.7 Overload Capability.
3
230 V
10.7 Overload Capability
The low overload means that if 110% of the continuous current (I
L
) is required for 1 minute every 10 minutes, the remaining 9 minutes
must be approximately 98% of I
L
or less. This is to make sure that the output current is not more than I
L
during the duty cycle.
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
124 | Danfoss A/S © 2019.05