10.8.6 Brake Resistance and Brake Power, Mains Voltage 380–500 V
Table 44: The Minimum Brake Resistance and Brake Power, Mains Voltage 380–500 V
Enclosure size The minimum brake resistance [Ω]
Brake power @845 VDC [kW]
(1)
MR4 63.0 11.3
MR5 41.0 17.0
MR6 21.0 34.0
MR7 14.0 51.0
MR8 6.5 109.9
MR9A 3.3 216.4
MR9B 1.4 250
1
When using recommended resistor types.
10.8.7 Brake Resistance and Brake Power, Mains Voltage 525–600 V
Table 45: The Minimum Brake Resistance and Brake Power, Mains Voltage 525–600 V
Enclosure size The minimum brake resistance [Ω]
Brake power @1014 VDC [kW]
(1)
MR5 100 7.5
MR6 30 22.4
MR7 18 44.8
MR8 9 93.3
MR9A 7 145
MR9B 2.5 183
1
When using recommended resistor types.
10.8.8 Brake Resistance and Brake Power, Mains Voltage 525–690 V
Table 46: The Minimum Brake Resistance and Brake Power, Mains Voltage 525–690 V
Enclosure size The minimum brake resistance [Ω]
Brake power @1166 VDC [kW]
(1)
MR6 30 30
MR7 18 55
MR8 9 110
MR9A 7 193
MR9B 2.5 250
1
When using recommended resistor types.