Enclo-
sure
size
Drive type I
L
[A] Fuse
(gG/gL)
[A]
Mains, motor, and brake
resistor
(1)
cable Cu [mm
2
]
Mains terminal cable size
[mm
2
]
Grounding ter-
minal cable size
[mm
2
]
MR8 0140 2
0140 5
140.0 160 3x70+35 (Cu)
3x95+29 (Al)
Bolt size M8 Bolt size M8
0170 2
0170 5
170.0 200 3x95+50 (Cu)
3x150+41 (Al)
Bolt size M8 Bolt size M8
0205 2
0205 5
205.0 250 3x120+70 (Cu)
3x185+57 (Al)
Bolt size M8 Bolt size M8
MR9A 0261 2
0261 5
261.0 315 3x185+95 (Cu)
2x(3x120+41) (Al)
Bolt size M10 Bolt size M8
0310 2
0310 5
310.0 350 2x(3x95+50) (Cu)
2x(3x120+41) (Al)
Bolt size M10 Bolt size M8
MR9B 0386 5 385.0 400 2x(3x120+70) (Cu)
2x(3x185+57) (Al)
Bolt size M10 Bolt size M8
1
If you use a multi-conductor cable, 1 of the conductors of the brake resistor cable stays unconnected. It is also possible to use a single cable if you obey the minimum cross- sectional
area of the cable.
10.3.3 Cable and Fuse Sizes, Mains Voltage 525–690 V
Table 25: Cable and Fuse Sizes, Mains Voltage 525–690 V
Enclo-
sure
size
Drive Type I
L
[A] Fuse
(gG/g
L) [A]
Mains, motor, and brake resistor
(1)
cable Cu [mm
2
]
Mains terminal cable size
[mm
2
]
Grounding
terminal ca-
ble size
[mm
2
]
MR5 0004 6 3.9 6 3x1.5+1.5 1–10 Cu 1–10
0006 6 6.1 10 3x1.5+1.5 1–10 Cu 1–10
0009 6 9.0 10 3x2.5+2.5 1–10 Cu 1–10
0011 6 11.0 16 3x2.5+2.5 1–10 Cu 1–10
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 107
Danfoss A/S © 2019.05