On delivery of the AC drive, the control unit contains the default control interface (graphical keypad). If special options were selected in
the order, the option boards are included loose in the delivery. On the next pages, there is information on the terminals and general
wiring examples.
It is possible to use the drive with an external power source with these properties: +24 V DC ±10%, minimum 1000 mA. Connect the
external power source to terminal 30. This voltage is sufficient to keep the control unit on and for setting the parameters. The
measurements of the main circuit (for example, the DC-link voltage, and the unit temperature) are not available when the drive is not
connected to mains.
The status indicator on the control unit shows the status of the drive. The status indicator is located in the control panel, below the
keypad, and it can show five different statuses.
Table 16: Control Unit LED Status Definitions
Color/status of the LED Status of the drive
Blinking slowly Ready
Green Run
Red Fault
Orange Alarm
Blinking fast Downloading software
7.2 Control Unit Cabling
7.2.1 Selection of the Control Cables
NOTICE
CABLE SELECTION
Obey regional low-voltage standards in the cable selection.
The control cables must be a minimum of 0.5 mm
2
(AWG20) multi-core shielded cables. The terminal wires must be a maximum of 2.5
mm
2
(AWG13) for the relay board terminals and other terminals.
Table 17: The Tightening Torques of the Control Cables
Terminal Terminal screw size Tightening torque
(Nm)
Tightening torque (lb-in)
All the terminals of the I/O board and the relay board M3 0.5 4.5
7.2.2 Control Unit Terminals
Here is the basic description of the terminals of the default I/O and relay board. The standard I/O board has 22 fixed control terminals
and 8 relay board terminals.
Some terminals are assigned for signals that have optional functions that can be used with the DIP switches. For more information, see
7.3 DIP Switches on the Control Unit.
Control Unit
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 65
Danfoss A/S © 2019.05