5.3.3 Necessary Quantity of Cooling Air
Table 13: The Necessary Quantity of Cooling Air
Enclosure size
The quantity of cooling air, m
3
/h
The quantity of cooling air, CFM
MR4 45 26
MR5 75 44
MR6 190 112
MR7 185 109
MR8 335 197
MR9 620 365
Mounting
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
30 | Danfoss A/S © 2019.05