Illustration 7: Installation Space when Drives Are Installed on Top of Each Other
If many AC drives are installed above each other, the necessary free space is C + D (see illustration 6).
Make also sure that the outlet air from the lower drive goes to a different direction than the air intake of the top drive. To do this,
attach a metal plate to the cabinet wall between the drives.
When the drives are installed in a cabinet, make sure to prevent recirculation of air.
Mounting
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 29
Danfoss A/S © 2019.05