Table 12: Minimum Clearances around the AC Drive in mm (in inch)
Enclosure size
A
(1)
B
(1)
C D
MR4 20 (0.8) 20 (0.8) 100 (3.9) 50 (2.0)
MR5 20 (0.8) 20 (0.8) 120 (4.7) 60 (2.4)
MR6 20 (0.8) 20 (0.8) 160 (6.3) 80 (3.1)
MR7 20 (0.8) 20 (0.8) 250 (9.8) 100 (3.9)
MR8 20 (0.8) 20 (0.8) 300 (11.8) 150 (5.9)
MR9 20 (0.8) 20 (0.8) 350 (13.8) 200 (7.9)
1
For a drive with IP54/UL Type 12, the minimum clearances A and B are 0 mm/0 in.
Mounting
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711