Enclosure
size
Drive type I
L
[A] Fuse
(Class T/J)
[A]
Mains, motor and
brake resistor
(1)
ca-
ble Cu [AWG]
Mains terminal cable size
[AWG]
Grounding terminal
cable size [AWG]
MR6 0038 5 38.0 50 4 13–0 13–2
0048 2
0046 5
48.0
46.0
60 4 13–0 13–2
0062 2
0061 5
(2)
62.0
61.0
80 4 13–0 13–2
MR7 0075 2
0072 5
75.0
72.0
100 2 9–2/0 9–2/0
0088 2
0087 5
88.0
87.0
110 1 9–2/0 9–2/0
0105 2
0105 5
105.0 150 1/0 9–2/0 9–2/0
MR8 0140 2
0140 5
140.0 200 3/0 1 AWG–350 kcmil 1 AWG–350 kcmil
0170 2
0170 5
170.0 225 250 kcmil 1 AWG–350 kcmil 1 AWG–350 kcmil
0205 2
0205 5
205.0 250 350 kcmil 1 AWG–350 kcmil 1 AWG–350 kcmil
MR9A 0261 2
0261 5
261.0 350 2x250 kcmil 1 AWG–350 kcmil 1 AWG–350 kcmil
0310 2
0310 5
310.0 400 2x250 kcmil 1 AWG–350 kcmil 1 AWG–350 kcmil
MR9B 0386 5 385.0 500 2x250 kcmil 1 AWG-350 kcmil 1 AWG-350 kcmil
1
If you use a multi-conductor cable, 1 of the conductors of the brake resistor cable stays unconnected. It is also possible to use a single cable if you obey the minimum cross-sectional
area of the cable.
2
To obey the UL regulations with the 500 V drive, it is necessary to have cables with a +194 °F heat resistance.
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
110 | Danfoss A/S © 2019.05